Ratings
Standby 700 kVA / 560 kW
Prime 635 kVA / 508 kW
Refer to ratings definitions on product data sheet
Ratings at 0.8 power factor
Complete genset designed and built at ISO9001 certified facility
Engine:
Perkins model – 2806A-E18TAG2
Industrial water cooled diesel
Electronic Governor
24VDC electrical system inc battery
Cooling pack suitable for 50oC ambient temperatures (open gensets)
Fully guarded fan, fan drive and charging alternator
|
Fuel Consumption
|
50 Hz
|
|
|
Standby
|
Prime
|
|
100% load
|
140.0 L/hr
|
125.6 L/hr
|
|
75% load
|
102.9 L/hr
|
93.2 L/hr
|
|
50% load
|
70.6 L/hr
|
65.0 L/hr
|
Refer to product data sheet for full test conditions
Alternator:
Olympian model – LL7024H
SHUNT excitation, brushless
Class H
Drip proof (IP23) air intake
Control Panel:
Powerwizard 2.0 digital control panel
Circuit Breaker:
3-pole MCCB
Standard Accessories
Battery Charger with Boost
Coolant Heater
Documentation:
Operation and maintenance manual
Wiring diagrams
Warranty:
All equipment carries full manufacturer’s warranty