Ratings
Standby 605 kVA / 484 kW
Prime 550 kVA / 440 kW
Refer to ratings definitions on product data sheet
Ratings at 0.8 power factor
Complete genset designed and built at ISO9001 certified facility
Engine:
Perkins model – 2806A-E18TAG1
Industrial water cooled diesel
Electronic Governor
24VDC electrical system inc battery
Cooling pack suitable for 50oC ambient temperatures (open gensets)
Fully guarded fan, fan drive and charging alternator
|
Fuel Consumption
|
50 Hz
|
|
|
Standby
|
Prime
|
|
100% load
|
122.5 L/hr
|
110.8L/hr
|
|
75% load
|
92.9L/hr
|
83.9L/hr
|
|
50% load
|
64.2L/hr
|
59.2 L/hr
|
Refer to product data sheet for full test conditions
Alternator:
Olympian model – LL6114G
SHUNT excitation, brushless
Class H
Drip proof (IP23) air intake
Control Panel:
Powerwizard 2.0 digital control panel
Circuit Breaker:
3-pole MCCB
Standard Accessories
Battery Charger with Boost
Coolant Heater
Documentation:
Operation and maintenance manual
Wiring diagrams
Warranty:
All equipment carries full manufacturer’s warranty