Ratings
Standby 50 kVA / 50 kW
Prime 45 kVA / 45 kW
Refer to ratings definitions on product data sheet
Ratings at 1.0 power factor
Complete genset designed and built at ISO9001 certified facility
Engine:
Perkins model – 1103A-33TG2
Industrial water cooled diesel
Mechanical Governor
12VDC electrical system inc battery
Cooling pack suitable for 50oC ambient temperatures (open gensets)
Fully guarded fan, fan drive and charging alternator
|
Fuel Consumption
|
50 Hz
|
|
|
Standby
|
Prime
|
|
100% load
|
15.6 L/hr
|
13.8 L/hr
|
|
75% load
|
11.3 L/hr
|
10.2 L/hr
|
|
50% load
|
7.8 L/hr
|
7.1 L/hr
|
Refer to product data sheet for full test conditions
Alternator:
Olympian model – LL2014J
SHUNT excitation, brushless
Class H
Drip proof (IP23) air intake
Control Panel:
Powerwizard 1 digital control panel
Circuit Breaker:
3-pole MCB
Documentation:
Operation and maintenance manual
Wiring diagrams
Warranty:
All equipment carries full manufacturer’s warranty